Mineral insulated cables can be butted using intermediate connectors of mineral insulated cables, Let VGCABLE introduce How do micc cable dock? Mineral insulated cable connection method.
Methods for installation of single - core and multi - core intermediate connectors for mineral insulated cables
Installation steps of intermediate connector for single core mineral insulated cable
1.Strip cable copper sheath
Strip cable copper sheath
2.Apply hot glue seal
3.Moisture expulsion (50~80CM) from the top down
Moisture expulsion (50~80CM) from the top down
4.The insulation resistance of cable conductor and sheath should be more than 100 megohm
The insulation resistance of cable conductor and sheath should be more than 100 megohm
5.Sleeve heat shrinkable tube
Sleeve heat shrinkable tube
6.Set on the accessories
Set on the accessories
7.Install and shrink heat shrinkable tubes
Install and shrink heat shrinkable tubes
8.Assemble intermediate connector to protect copper tube
Assemble intermediate connector to protect copper tube
9.Install intermediate connector to protect copper tubing
Install intermediate connector to protect copper tubing