Position: Home > Rubber Cable > H07rn-f Cable > Article
What's cable type ho7 spec? ho7 cable ratings,diameter,data sheet & suppliers
Ho7 is short for h07rn-f cable, Let VGCABLE introduce What is cable type ho7 spec? ho7 cable ratings,diameter,data sheet & suppliers.
1.Cable type ho7 spec
Applicable standard: IEC 60245-4 / GB/T 5013.4Flame retardance: IEC 60332-1 / GB/T 18380.1
Conductor: Plain or tinned annealed copper, IEC 60228 / GB/T 3956 Class 5
Insulation: Ethylene-propylene rubber (EPR) compound, type IE4
Sheath: Rubber compound, type SE3, Polychloroprene (PCP) compound, type SE4
Core identification: single core: black
2 core: Blue & brown
3 core: Blue, brown & green/yellow
4 core: Black, brown, grey & green/yellow
5 core: Black, blue, brown, grey & green/yellow
7 cores and above are numbered
Sheath/Jacket: PCP (Polychloroprene) more commonly referred to as OFR
(Oil resistant & flame retardant)
Colour: Black
Voltage: 450/750v
Operating temperature: Maximum 60°C,
Minimum bending -30°C
Minimum bending radius: 6 x overall diameter for cables not exceeding 25mm O/D
8 x overall diameter for cables exceeding 25mm O/D
Standards: BS6500: electrical cables for use with appliances and equipment intended for domestic, office and similar environments
BS7919: Electric cables. Flexible cables rated up to 450/750V for use with appliances and equipment intended for industrial and similar environments
Class 5
CPR Fire Class ECA
2.Ho7 cable ratings
Current-carrying capacity and mass supportable (1 mm² to 2.5 mm²)h07rn-f Current-carrying capacity and mass supportable (1 mm² to 2.5 mm²)
Current-carrying capacity (4 mm² and above)
h07rn-f current, Current-carrying capacity (4 mm² and above)
3.Ho7 cable diameter & ho7 cable data sheet
![Ho7 cable diameter & ho7 cable data sheet](/uploads/allimg/200310/1-200310105441300.gif)
![Ho7 cable diameter & ho7 cable data sheet](/uploads/allimg/200310/1-200310105530F6.gif)
![Ho7 cable diameter & ho7 cable data sheet](/uploads/allimg/200310/1-200310105520c9.gif)
![Ho7 cable diameter & ho7 cable data sheet](/uploads/allimg/200310/1-200310105512159.gif)
H07RN-F cable Static Use Bend Radius: 3 x outer diameter (for Ø < 12 mm) or 4 x (for Ø > 12 mm).